BS 6622 Single Core Unarmoured (Copper Wire Screen) 15KV XLPE Stranded Copper Conductors
Construction
| Cross-sectional area mmsq | Minimum average thickness of insulation mm | Nominal diameterover insulation  | Nominal area of copper wire screen  mm sq | Nominal thickness of PVC oversheath mm | Nominal overall diameter of cable mm | 
| 70 | 4.5 | 21.2 | 16 | 1.8 | 28.1 | 
| 95 | 4.5 | 22.9 | 16 | 1.9 | 30.1 | 
| 120 | 4.5 | 24.4 | 16 | 1.9 | 31.8 | 
| 150 | 4.5 | 25.7 | 16 | 2 | 33.1 | 
| 185 | 4.5 | 27.5 | 16 | 2 | 35.1 | 
| 240 | 4.5 | 29.7 | 25 | 2.1 | 37.3 | 
| 300 | 4.5 | 32.0 | 25 | 2.2 | 39.8 | 
| 400 | 4.5 | 34.7 | 35 | 2.3 | 42.7 | 
| 500 | 4.5 | 37.6 | 35 | 2.4 | 45.9 | 
| 630 | 4.5 | 41.5 | 35 | 2.5 | 50.0 | 
Installation
| cross-sectional area mmsq  | Approximate cable weight kg/m | Nominal drum length  m | Minimum bending radius mm  | Nominal  internal diameter of ducts mm  | 
| 70 | 0.9 | 1000 | 550 | 100 | 
| 95 | 1.1 | 500 | 550 | 100 | 
| 120 | 1.2 | 500 | 600 | 100 | 
| 150 | 1.3 | 500 | 600 | 100 | 
| 185 | 1.5 | 500 | 650 | 100 | 
| 240 | 1.8 | 500 | 700 | 100 | 
| 300 | 2 | 500 | 750 | 100 | 
| 400 | 2.5 | 500 | 800 | 100 | 
| 500 | 2.9 | 500 | 850 | 100 | 
| 630 | 3.4 | 400 | 900 | 100 | 
Electrical Performance
| cross-sectional area mmsq | Maximum DC resistance of conductor at 20 
    
     ℃
    
uohms/m  | Maximum AC resistance of conductor at 90 ℃ uohms/m  | Reactance at 50Hz  uohms/m | Impedance at 50Hz uohms/m | Maximum Capacitace PF/m | Maximum charging current at normal voltage and frequency mA/m  | 
| 70 | 443.0 | 568 | 127 | 582 | 232 | 0.63 | 
| 95 | 320.0 | 410 | 120 | 427 | 258 | 0.70 | 
| 120 | 253.0 | 325 | 116 | 345 | 281 | 0.77 | 
| 150 | 206.0 | 365 | 112 | 288 | 301 | 0.82 | 
| 185 | 164.0 | 211 | 109 | 237 | 329 | 0.9 | 
| 240 | 125.0 | 161 | 105 | 192 | 363 | 0.99 | 
| 300 | 100.0 | 130 | 101 | 165 | 398 | 1.09 | 
| 400 | 77.8 | 102 | 97.9 | 141 | 439 | 1.2 | 
| 500 | 60.5 | 81 | 95.1 | 125 | 483 | 1.32 | 
| 630 | 46.9 | 64 | 91.5 | 112 | 542 | 1.46 | 
Ratings
| Cross-sectional area  mmsq | Laid direct in ground Amps | Drawn into ducts Amps | Laid in air Amps | One second short circuit rating of conductor KA | One second short circuit rating of copper per core KA | 
| 70 | 210 | 215 | 240 | 6.3 | 2.6 | 
| 95 | 250 | 255 | 300 | 8.5 | 2.6 | 
| 120 | 280 | 285 | 355 | 11 | 2.6 | 
| 150 | 320 | 315 | 380 | 13.5 | 2.6 | 
| 185 | 360 | 350 | 435 | 17 | 2.6 | 
| 240 | 415 | 405 | 510 | 22.3 | 4.3 | 
| 300 | 475 | 455 | 600 | 28 | 4.3 | 
| 400 | 540 | 510 | 700 | 36.6 | 5.8 | 
| 500 | 610 | 570 | 810 | 46.2 | 5.8 | 
| 630 | 680 | 640 | 930 | 58.3 | 5.8 | 